Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

robertlabrie

Starting Member

1

Saturday, July 16th 2016, 2:17pm

How to install a valve to blow out sprinklers

Hi,

I have a 3 zone system with 1" lines. The water meter is at the curb, with a manual shut off value for the system immediately past the meter. The solenoid valves are next to the house, around 50 feet away, below grade in a box. The valves are Irritrol, most of the rotors are Hunter, with some Irritrol and consumer grade Rainbird mixed in. I'll gladly replace any rotor that could be a problem. I'm in suburban Atlanta, zone 7b.

I want to put a valve onto the system so that I can have someone blow it out in the fall. My question is: Do I put it after the solenoids, on each zone, or on the main line, before the solenoids? As best as I can tell, these Irritrol valves cannot be opened manually, but they have a flow regulator. They're model 205tf.

Should I even bother with a blow out in this zone? I'm wondering if just opening the valve housing to drain out the lines in the fall is good enough.

Thanks,
Rob

Wet_Boots

Supreme Member

Posts: 5,135

Location: Metro NYC

2

Saturday, July 16th 2016, 3:25pm

You cut in a boiler drain just downstream of the system shutoff valve, and that's your blowout valve.