Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

SLMC

New Member

1

Wednesday, July 29th 2015, 4:00pm

Hunter XC 6 zone system - self test shows no issues, but Ohm meter disagrees

System is 7 years old. Last fall it was fully functional. This year not so much. Voltage is good to the controller and all valves. With the master open, I can manually open 5 of 6 valves and run those zones. At this time, I can't find the zone 6 valve. Ohm meter shows proper resistance on zones 3,4,5. I'm going to double check, but I believe it's showing "OL" for the master,1,2, and 6. This suggests a broken wire, but shouldn't the controller self test show that? The self-test feature shows no issues at all. Also, master,1 & 2 valves are all located on the same side of the house. Is it logical to assume that the zone 6 valve is located in that area as well?

Wet_Boots

Supreme Member

Posts: 5,198

Location: Metro NYC

2

Wednesday, July 29th 2015, 5:33pm

trust your multimeter more than you trust a controller

SLMC

New Member

3

Thursday, July 30th 2015, 2:21pm

Next question - the bundle of wires at the controller is multi-color, like thermostat wiring. The wiring at the valves is all red & white. Am I missing something? Is there nest of wires where each color has been spliced to a generic red wire? One would hope that it's in a box, but I haven't seen it. This is maybe not the Cadillac of irrigation installs.

Wet_Boots

Supreme Member

Posts: 5,198

Location: Metro NYC

4

Friday, July 31st 2015, 7:49am

You may have a master valve, in its own valve box, where the wires transition to heavier-gauge white and red, which go out into the field, each valve in its own small round box.

SLMC

New Member

5

Friday, July 31st 2015, 1:55pm

I have a master in a round box, between the main water line and the backflow preventer. Wires to it are just red & white. I do have 6 zone valves in individual round boxes. If I lost the master & 1,2, and 6 at the same time, I'm guessing that transition point is very likely the source of the issue. The controller will run 3,4 & 5 if I open the master manually. So start digging where the wires exit the garage & hopefully the transition point is close?

Wet_Boots

Supreme Member

Posts: 5,198

Location: Metro NYC

6

Saturday, August 1st 2015, 5:57am

post a photo of this 'backflow preventer'
you have the right idea about the wire transition

SLMC

New Member

7

Tuesday, August 4th 2015, 5:50pm

Photos to come. I'm getting close to the transition point of color to red zone wiring. I'm pretty sure it's just buried in the dirt & not enclosed or protected in any way. Hoping that will reveal some obvious issues... *edit* Can't seem to attach photos. Wire transition is just a nest of wires buried in the yard. Field wires for the three working zones are all routed to the left, where they would continue along the side of the house & meet those 3 valves. There is also a common wire routed to the left. Field wires for the non-working zones are all routed to the right - so they apparently go under the fence and driveway & continue along the other side of the house to meet those valves. I also found a loose piece of white wire that looks like the common wire. Not sure if that should be connected or if it's a random bit of scrap wire.

This post has been edited 2 times, last edit by "SLMC" (Aug 5th 2015, 12:39pm)


SLMC

New Member

8

Wednesday, August 5th 2015, 12:55pm

Sorry for the stream of consciousness posts. I'm thinking if the system was wired with a set of 3 valves on one side of the house & 4 on the other, then I should have a common wire run for each side. It would explain why the controller self test didn't find any issues. Worth a shot-
*edit* BOOM. Done. Problem solved. Thinking I might go ahead and recap all my transition wires and maybe put that in a housing of some sort.

This post has been edited 1 times, last edit by "SLMC" (Aug 5th 2015, 1:37pm)