My supply line to the house was 1", and I ended up using 1-1/2 pipe for my mainline. Why 1-1/2 do you ask, well becuase I had 400' of mainline to get all the way to the back of my house. I used the larger pipe for 2 reasons, the pressure loss in 1-1/2 pipe was less than 1-1/4, and it also turned out that the 1-1/2 pipe was cheaper.
I ended up having to use a RPZ valve (1"), which I installed right near my 1" supply line, and then stepped up my mainline to 1-1/2 right after the backflow.
I would at least use SCH40 for your above ground connection, as the cl200 pipe would be too thin walled. You could always check with the inspector to see what's required.