Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.


Starting Member


Sunday, September 29th 2002, 5:31am

Backflow devise

What depth can a backflow devise be installed in the ground?


Supreme Member

Posts: 456

Location: USA


Sunday, September 29th 2002, 10:49am

I install them in the ground at 18" at the most. But I mostly install PVB's above the ground 18" Because they are easier to service and repair.


Active Member


Thursday, July 24th 2003, 4:02pm

Unless rise or drop from you heads is an overriding concern, bury it only as far down as you can reach and easily service the device.

Rays Sprinklers

Supreme Member

Posts: 493

Location: USA


Tuesday, August 19th 2003, 1:48pm

The PVB is easier to service becuase it is out of the ground....the double check is installed out of the way up to 18" deep at the most.......any deeper and you will have trouble serviceing and shutting it off if you have to.......install them deep enough to be covered and have the valve box level with the ground that it is to be buried in!