I installed a new 3/4" PVB that goes to a 1" before reaching the valves. Could that cause the PVB to vibrate and spit water for up to a minute when the system is starting up? I checked the inside parts and they all look OK. It's a brand new PVB so I'm stumped. Any ideas?
It's a Conbraco 4A-504-02F 3/4 in. First couple of times it ran fine with no noises. Today I tried to see if it was a valve problem. Changed 3 of the diaphragms on the older valves and tried to isolate them. So when I start the system without 2 of the valves on there is no noise at all. Could this be a valve problem instead? The 2 valves in question are quite old.
Any time a PVB spills water, it is telling you the system design is suspect, because the water pressure should not be dropping so low when a valve opens. If your valves had flow controls, you could throttle them down.