Thursday, July 8th 2010, 1:01pm

No problem installing an RPZ indoors, that is, if it is installed in a room with a floor drain capable of handling the entire flow of the sprinkler system. Lacking that, they go outdoors.

secutanudu

Active Member

Posts: 36

Location: Guilderland, NY (Near Albany)

52

Thursday, July 8th 2010, 1:52pm

No problem installing an RPZ indoors, that is, if it is installed in a room with a floor drain capable of handling the entire flow of the sprinkler system. Lacking that, they go outdoors.
Then outdoors it is. Thanks.

Fireguy97

Advanced Member

Posts: 73

Location: Kamloops, In Beautiful British Columbia

53

Thursday, July 8th 2010, 11:16pm

What make/model RPZ would you guys recommend?

Thoughts on Lead Free?

Thanks.



I've been looking at the WIlkins 375. It has Blow Out and Flush (BOF) module that you can get if you're in a cold weather climate. At the end of the season when you blow out your system, you just have to undo two screws and remove the entire check valve chamber. You then insert the BOF. The BOF has two FIP ports that you can insert adapters for whatever type of air fitting you need for blow out. You keep the BOF in over the winter, and In the spring you just use the BOF to flush your RP and sprinkler system before you turn it on. When your backflow assembly tester comes, you can reinsert the check valve chamber and have it tested.

A lot of my client remore their entire unit every winter to protect it from freezing. This should put and end to that.

www.zurn.com/operations/wilkins/pdfs/CutSheets/WK-375-CS%200410.pdf

I ordered one and got the call today that it's in.

Mick
Irrigation Contractor

Certified Backflow Assembly Tester

This post has been edited 1 times, last edit by "Fireguy97" (Jul 8th 2010, 11:24pm)


secutanudu

Active Member

Posts: 36

Location: Guilderland, NY (Near Albany)

54

Sunday, July 11th 2010, 9:52am

Have you tried the wilkins 375 yet? It seems interesting...I like that you can remove the guts for the winter.

If so...thoughts?

Fireguy97

Advanced Member

Posts: 73

Location: Kamloops, In Beautiful British Columbia

55

Wednesday, July 14th 2010, 12:24am

Have you tried the wilkins 375 yet? It seems interesting...I like that you can remove the guts for the winter.

If so...thoughts?

Just installed it today.

Looks good to me. Easy removal and re-installation of the BOF and the check chamber. If anything has to be repaired in the check valves, you can replace the rubber only, you can replace check valve 1 and/or check valve two. Both of those options are the same as with any other RP, but with this on you also have a third option. You can also replace the entire chamber. For you that might be a little on the expensive side, to do that. But for me as when I test and repair, I can replace the chamber and repair it later in the shop and keep the newly repaired unit for the next RP repair.

I'll be getting more of these and the double check version, the 350.


Mick
Irrigation Contractor

Certified Backflow Assembly Tester

Similar threads

Rate this thread
AUUSAUK Businessroller chainroller chain manufacturers Motorcycle ChainTransmission chain Converor chain AU手机铃声手机铃声免费下载qq分组益智游戏公司袜子批发袜子批发厂家袜子批发价格外贸袜子批发UK Company
608565 326714 62341 170063 138723 345908 592812 186859 200626 351384 210832 327991 468332 171538 3465 146376 110214 534667 603880 614931 771710 500008 1777119 1700764 906588 776880 1578585 663247 1108594 598575 175788 541154 1562803 1976342 1963804 110391 1369510 823035 447073 227052 1026978 1376232 478243 1892869 2090037 2598674 445248 1870660 1091863 465726 1530562 1894735 2198751 544990 960549 1629329 1552087 1093095 1077490 133307