Sunday, May 31st 2015, 10:26am

Author: JERRYCOLLINS

Zone leak--continuous-24/7

One thing that still puzzles me is the layout of the main one inch line. From the back flow check valve and ball shut off, that I installed, the main valve was 70' away and had 2 branch lines before the main valve and four branch lines after the main valve. What is the purpose of this? As I have 7 zones in the front and 7 in the back--maybe there is another main??

Saturday, May 30th 2015, 3:57pm

Author: JERRYCOLLINS

Zone leak--continuous-24/7

Finally---after 4 days of digging, cutting pipe, wires, etc--problem solved. Mr Fixit--a big thank you..! I verified the found valve was indeed a main valve as I cut the line, capped it off--and none of my zones worked. This valve was in line to the actual zone valve we fixed. Replaced with new valve and everything normal--including leak. The zone valve on the one inch incoming line must have been missed by the crew that redid the sprinkler system in 2003. From this old valve it ran to three spr...

Saturday, May 30th 2015, 6:32am

Author: JERRYCOLLINS

continuous leak

You were correct. In 2003 a major landscaping job was completed. Found a zone valve in the main incoming 1" line, downstream of 2 other branches. I believe this was abandoned. Assume i should take this out? Have narrowed the single zone leak to 1--. this zone valve on the incoming to my new zone valve and 2.-- a 3' section of the feeder line 3/4"

Friday, May 29th 2015, 7:35am

Author: JERRYCOLLINS

Zone leak--continuous-24/7

still digging and repairing cut lines and 30 yrs of roots

Wednesday, May 27th 2015, 7:28am

Author: JERRYCOLLINS

Zone leak--continuous-24/7

As you suspected, we have found a modification in this zone. Have not yet uncovered another valve--Have 3/4 of the entire zone uncovered. Will complete by the end of the day and will let you know. thanks

Monday, May 25th 2015, 8:34pm

Author: JERRYCOLLINS

correct valve

We know we have the correct valve--loosen the solenoid and the zone works normally. Close the solenoid and the spray stops--but leaks. Have installed an additional ball valve on incoming line to this zone valve..leak continuues. It must have a secondary source of incoming. Leak only stops when main source valve is closed for all zones. Still digging up the entire pipeline Need better ideas !

Sunday, May 24th 2015, 4:07pm

Author: JERRYCOLLINS

Zone leak--continuous-24/7

Have only one zone with problem--system is more than 10 yrs old. I replaced one valve with a new one--not one from the same batch I put a ball shutoff valve in the line before the zone valve-since even this did not stop the leak---I can't see how any valve will help? I am in the process of digging up the entire zone trying to ID the source of the additional water in the line.

Sunday, May 24th 2015, 7:14am

Author: JERRYCOLLINS

Zone leak--continuous-24/7

History:- 1 Replaced valve gasket 2 Replaced with new valve; purged; etc 2b switched solenoid with known good solenoid 3 Checked new valve gasket: purged; etc 4 Installed check valve; purged; etc 5 Installed new ball valve inline with zone valve(incoming water)--can not believe this did not stop leak 6 Closed ball valve on main incoming line, down stream of back flow preventer--this stops leak 7 Ordered 12 sprinkler head check valves from Irritrol. these changes were made over a one week time--t...

Wednesday, May 6th 2015, 2:03pm

Author: JERRYCOLLINS

leaking zone

Replacement part identical. Tightened solenoid--no change. took off bonnet inspected diaphram--no issues. purged system replaced diaphragm and bonnet; turned on main line valve--and YES it stopped leaking (for 10min) . I manually started the zone, ran for 5 min shut down--and the *(^*&(^9969)(*&*&^ is leaking again?????? Shut off incoming line Edit--checked control box 2 X 7 wires--no other connections--so I guess no master valve. Now my master is manual and when it is off the is no leaking

Wednesday, May 6th 2015, 7:57am

Author: JERRYCOLLINS

master valve

We installed the shut off valve downstream of the backflow unit. Is it possible their is no master valve? Back to Google jerry

Wednesday, May 6th 2015, 7:50am

Author: JERRYCOLLINS

zone valve

We did several things for this problem. Yes, activating the specific zone valve activates the heads normally--and the leak continuues--we did this several times. Also we installed a shut off valve in the main incoming sprinkler line. Shut it off overnight, opened the next morning and same problem--24/7 leak. Activated and ran entire 14 zone system--leak continuues. Shut incoming line off. Not sure what you mean by Master valve? Will google waiting for your reply and TIA jerry in Savannah

Tuesday, May 5th 2015, 4:48pm

Author: JERRYCOLLINS

sprinkler valve

Have a 14 zone Rainbird system. Have one zone that leaks 24/7. Checked diaphragm, no issues seen: replaced entire valve and system heads still leaked. Replaced valve--followed directions and bled/purged system for 1 minute--no change--entire zone still leaks ?? jerry