You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 4180 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 10 posts

Monday, June 16th 2003, 4:04am

by drpete3

I suggest going to your local commercial plumbing supply store and ask them. They will tell you what you need and can explain why that particular pump is sufficient. Their seems to be so many different pumps it is best to ask professionals.


Saturday, June 14th 2003, 2:18pm

by RVLI

I don't know about pumps very well, but most irrigation systems I've seen running on a pump are on Goulds pumps.


Saturday, June 14th 2003, 1:21pm

by fwinns5

I would like to suck water from a pond for my sprinkler system. The pump will be 10 ft from the water and about 3 ft above the water. The furthest heads will be about 100 ft from the pump and 15 ft above the pump. What size and/or brand pump do you recommend? Any input appreciated.


Thursday, June 12th 2003, 5:37pm

by Rays Sprinklers

<img src=icon_smile.gif border=0 align=middle>

Thanks
Ray
Rays Above and Beyond Automatic Lawn Sprinklers

Thursday, June 5th 2003, 9:02am

by drpete3

Overall I agree with ray and rvli but I think he makes a good point in that if you a covering long distances then the horse shoe design is a good idea from the stand point of pressure loss. But, why couldnt you use the 1.25 poly throuhgout the entire system in that case?


Tuesday, June 3rd 2003, 7:07pm

by RVLI

I agree with Ray on this one. It would save you more money having two manifolds rather than spending more for extra wire and pipe.


Tuesday, June 3rd 2003, 7:56am

by Rays Sprinklers

We also put our valves in a grouped manifold either in the front or back, so there is not much of a length (no more than 20')and the lines run out of there!

Thanks
Ray
Rays Above and Beyond Automatic Lawn Sprinklers

Tuesday, June 3rd 2003, 7:54am

by Rays Sprinklers

True but around here we have about 85-105 PSI and eventually the lines can pop, or give out.........if there is a master valve than its okay, but i wouldnt use poly for the mainline..........just my way of doing things.....Poly isnt designed for constant water pressure

Thanks
Ray
Rays Above and Beyond Automatic Lawn Sprinklers

Saturday, May 31st 2003, 7:28am

by rbielak

<BLOCKQUOTE id=quote><font size=1 face="Verdana, Arial, Helvetica" id=quote>quote:<hr height=1 noshade id=quote>
Hey,
Waittttttt!!!!!!!! Poly is not to be used for the mainline (leading to valves) it will pop under constant pressure, there you need to use copper or PVC, and poly to the sprinklers
<hr height=1 noshade id=quote></BLOCKQUOTE id=quote></font id=quote><font face="Verdana, Arial, Helvetica" size=2 id=quote>

Are you saying that EVERYTHING before the valves (not the breaker, but the valves) needs to be copper or PVC? I TOTALLY disagree.

My mainline is a 300' piece of 1.25" 100psi poly buried in a horseshoe around my house. There's a 30 foot piece that runs from my vaccumn breaker to feed the mainline. About every 30 feet (on my poly mainline) is a 1.25 slip x 1.25 slip x 1" FPT that connects to a 1" jar-top valve (slips are double clamped on every connection). From the valves, I run 1" 100PSI poly to the heads.

I'm on a well with a 20 gpm 3/4 hp pump, which runs (average) 50 psi -- a 40 psi cut-on and a 60 psi cut-off switch settings.

I have NO manifolds built. Which means I used much less 1" poly (less pressure loss versus the 1.25" main to valves, less $$ wasted in 1" poly).

95% of the residential systems installed around here (MI) are designed and built this way -- IF the builder is any good.

Why, again, should I run copper or PVC instead of 100PSI 1.25" poly (330 feet worth)? There's no need.




Wednesday, May 28th 2003, 11:58am

by RVLI

Nope. You still consider the valves after your master valve on the mainline, so it still needs to be PVC or Copper. No Exception!