Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.
Attention: The last reply to this post was 806 days ago. The thread may already be out of date. Please consider creating a new thread.
The last 3 posts
Back in the day, I wouldn't even go much beyond 500 feet for 18 gauge, with tables giving about 800 feet max for 18 gauge. If only the common wire is upsized, that still greatly extends the total run available.
2000' is pushing it with 18awg multistrand. Not sure about the other gauges.
Voltage Loss= (10.4 x Length x Amps) / Circular Mills of Wire (1680 for 18awg)
I don't use any voltage loss greater than 4.5V
maximum length of wire to opperate a valve
I was curious to know how long you can run 18 gauge wire and still have enough voltage to opperate a valve? 16 and 14 too if you know.