You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 1685 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 4 posts

Tuesday, April 13th 2010, 11:01pm

by degree451

Awesome, just what I needed to confirm my thoughts. Thanks!

Tuesday, April 13th 2010, 10:16pm

by pass1

gpm and pipe size

Service line type and size along with static pressure is a start in determining your gpm capacity. You need to factor in such things as elevation and friction loss also. A bucket test is useful only if you draw the water from the pipe that is going to be your sprinkler water source . ( not a branched off hose bib)Never base a design solely on its results . Your test should have yielded a higher result at the higher pressure(45psi) I don't know what happened there , maybe you miscalculated???.
A larger pipe does not create more pressure, it just has less pressure loss through it at a given gpm than a smaller pipe .
Yes, there is a major difference in capacity between a 1/2" pipe and a 1" pipe.

Tuesday, April 13th 2010, 9:33pm

by HooKooDooKu

Yes the bucket tests are not accurate. Just read up on the subject at www.irrigationtutorials.com.
But the bucket test is in these brocures because it is easy.

Tuesday, April 13th 2010, 7:44pm

by degree451

Confused about GPM in books I picked up from the store

I followed the directions on a brochure and a sprinkler book to determine my static pressure and the GPM using a 5 gallon bucket. The results are as follows:

Static Pressure: 76

GPM at 40 PSI: 2.4

GPM at 45 PSI: 2.04



I just stopped there. The GPM are so low I would only be able to put 1 sprinkler head per zone with those numbers. After thinking about it a bit I see that the logic in the book and the brochure is completely asinine. You should be tying directly into the main line, not some 3/8 inch copper pipe which is what my faucets are. They tell you in this book to tie into the main line just five pages after telling you to determine your water capacity using your puny little faucet. So why are the people writing these brochures telling everyone to use their outside faucets to determine capacity? 3/8 vs 1 & ΒΌ is a big difference in throughput right? Have I gone off the reservation? Seems to me that the bigger the pipe the higher the pressure and the more GPM correct?