Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 2 posts

Wednesday, August 8th 2018, 12:01pm

by adam10

From your description it looks like you have a common wire problem. Check the resistance for each station against Valve Common. Probably all are open.

Monday, August 6th 2018, 5:13pm

by Pdeck08 (Guest)

Controller question

Zones 1-6 are all on the same common and are not working. When I checked the amps from controller to the valves, all 6 are reading 24 volts even when I turn on just one of the zones. What does that indicate as the problem when all zones are registering 24 volts at the same time?