You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 3166 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 10 posts

Tuesday, March 21st 2006, 10:56am

by lush96

woopie doo. im sure his is great advice. yours is not.

Tuesday, March 21st 2006, 4:10am

by Tom

yeah he could have lush96, but he was trying to explain to "swturner" how to find and fix the real problem so he would to be able to diagnose future valve problems. Tony aka sprinklerguy has operated a succesful sprinkler business in several states so his advice is valuable.


Sunday, March 19th 2006, 8:22pm

by lush96

this thread is so old. sprinklerguy could have ended it by just saying....."buy an entire new valve and replace the whole thing!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! duh!!!!!!!!!!!!!!

Thursday, February 16th 2006, 6:44pm

by SprinklerGuy

You do realize that this thread is almost 4 years old right?

Saturday, February 11th 2006, 8:48am

by rand651522

Quoted

<i>Originally posted by Patrick Graham</i>
<br />

Quoted

<i>Originally posted by swturner</i>
<br />

Sorry I was trying to respond to Patrick.The one thing you said about not being able to open the Zone at the Valve.You still can by just slighlty turning the solenoid counterclock-wise.Let it bleed off and you will be opening the valve right there.Hope this helps.[;)]

Saturday, February 11th 2006, 7:53am

by Patrick Graham

<blockquote id="quote"><font size="1" face="Verdana, Arial, Helvetica" id="quote">quote:<hr height="1" noshade id="quote"><i>Originally posted by swturner</i>
<br />Well, I did as suggested, and the problem remains...

I first tried replacing just the diaphram, and as you indicated it did not work well with the old bonnet. So I replaced the bonnet as well. I was careful to align the diaphram, etc. I was encouraged because when I tested it out before wiring up the solenoid, it appeared to work - I was surprised that the solenoid appeared to have the valve open by default.

So I turned the water back off at the supply, wired up the solenoid, and - darned if it doesn't behave just like the old one. It doesn't work unless I crack the bleeder valve just a tad. I'm wondering if there could be something broken about the anti-siphon part of the head? With this change, I've replaced all the moving parts, so maybe there's something stuck somewhere??

One other nit - the R-205TF I bought at your suggestion doesn't have a manual lever on its solenoid like the 2711APR did. This is annoying, as I liked being able to use that to open the lines for testing the heads, etc. Now I have to do all that from the timer panel, and if the circuit is broken it will be harder to diagnose.



<hr height="1" noshade id="quote"></blockquote id="quote"></font id="quote">

Sunday, June 16th 2002, 2:16pm

by swturner

I guess I must have somehow misaligned the solenoid nipple. I'm baffled as to how that could have been a problem at the start, but maybe there was blockage in there somehow.

Anyhow, I did as you suggested, and the new bonnet still didn't work. (No sign of an extra O-ring or retainer, and the solenoid popped in and out just fine.) In desperation, I replaced the *original* bonnet, and - miracle of miracles - it all seems to work now...

So, perhaps there was blockage in the bonnet to start with, because I used a paper-clip to clear the solenoid hole there, too. And perhaps I screwed up and mis-aligned the nipple when I installed the new bonnet. But however it works - I ain't touching it now!

Thanks a lot for the advice.



Monday, June 10th 2002, 3:59am

by SprinklerGuy

Under the solenoid in the bonnet is a port....looks like a "tit" for lack of a better word..sorry. This port is an "outie" and it goes into a port in the body of the valve that is an "innie". If either of these is plugged the valve will NOT WORK with the timer. Try this:

Turn the water off and remove the solenoid. Activate the timer, does the solenoid pull it's pin up? If so, the circuit is good. If not, the wires may be broken to that valve....

If the circuit is good: Check the ports, use a paper clip to ensure that they are clear....check your installation to make sure the ports line up correctly. If all that is good check this: Is there a white plastic retainer ring on the new solenoid? Remove it with needle nose pliers it should pop right out....DO NOT LOSE THE PIN THOUGH.....

Also, the new solenoid should have an o'ring inside of itself....no need for the oring that you may have taken out of the old bonnet....make sure there is NOT AN O'RING IN THE BONNET ITSELF right where the solenoid screws in......

Try all this and get back to me......sprinklersolutions@msn.com Good Luck! I'm with ya!

Sprinkler Solutions, Inc.
Arizona and Colorado
www.sprinklersolutions.net


Saturday, June 8th 2002, 11:06am

by swturner

Well, I did as suggested, and the problem remains...

I first tried replacing just the diaphram, and as you indicated it did not work well with the old bonnet. So I replaced the bonnet as well. I was careful to align the diaphram, etc. I was encouraged because when I tested it out before wiring up the solenoid, it appeared to work - I was surprised that the solenoid appeared to have the valve open by default.

So I turned the water back off at the supply, wired up the solenoid, and - darned if it doesn't behave just like the old one. It doesn't work unless I crack the bleeder valve just a tad. I'm wondering if there could be something broken about the anti-siphon part of the head? With this change, I've replaced all the moving parts, so maybe there's something stuck somewhere??

One other nit - the R-205TF I bought at your suggestion doesn't have a manual lever on its solenoid like the 2711APR did. This is annoying, as I liked being able to use that to open the lines for testing the heads, etc. Now I have to do all that from the timer panel, and if the circuit is broken it will be harder to diagnose.



Thursday, May 30th 2002, 11:41am

by SprinklerGuy

It's just that if you are going to all the trouble to open the valve up you may as well get it all done at once. And...cheaper to buy the entire valve than it is to buy it piece by piece.....Plus another problem with that particular valve is that sometimes the new diaphragms do not mesh well with the old bonnets....not worth messing with in my opinion. Take it from someone who has seen "murphy's law" at it's worst....do it all now and save some hassle.

Thanks