You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 3105 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 6 posts

Sunday, March 19th 2006, 7:32pm

by lush96

also check the power from your clock terminals too. if it shows power to each zone at the clock and not at the valves even after you have restripped and rewired then your actuall wire is bad somewhere down the line. if none of these troubleshoots work then for some freak reason all your valves went bad at once. very very unlikely though

Sunday, March 19th 2006, 7:28pm

by lush96

restrip and rewire the valves. corrosion on the commons is a common problem with this situation. if that doesnt work, it could still be your timer. turn a zone on.......go to the corresponding valve and make sure juice is reaching the valve. its highly unlikely that all your valves solenoids all went bad at once so its probably not that. so restrip and rewire, and then check the power going to the valves. 99 percent of the time that will be the solution.

Thursday, February 16th 2006, 6:41pm

by SprinklerGuy

WE need more info...

Pump?
Master valve?
Do the valves hum when the timer tells them to come on (yes laymans terms..hum)
Any digging lately that could have cut wires?
Do you know how to use an ohmeter?

Wednesday, February 8th 2006, 9:46am

by julieblades

Hi there,
Is there a filter on the system. If so is it blocked up? This often happens to me and it shuts everything down. Don't know how dirty your water is. Any isolation valves on the zones turned off? Master valve turned off? Where in the pipe did you check for pressure...mailine or lateral?
Hope this helps

Wednesday, February 8th 2006, 6:44am

by Wet_Boots

Go to the valves and check their manual operation. Check the wiring for continuity with a multimeter.

Monday, February 6th 2006, 8:35am

by jjgoss

All 6 zones out: Controller or Valves or?

Hi all -

Trying to troubeshoot. No water is coming out of the sprinklers in any of the 6 zones.

Here's what I know:

- Older Controller (non digital) is working. The timer kicks off the "dials" and it is rotating around. And when one zone is completed and goes to "OFF", the "dial" moves to the next zone and it "appears" that it is working, but no water.

- Checked the fuse. The fuse is ok.

- Dug up and cut into PVC pipe. Water pressure is fine.

- What else could it be?

Thanks, Jim