Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 4 posts

Wednesday, July 25th 2018, 11:18pm

by mrfixit

Does number 3 come on if you turn the master valve on manually at the valve? By opening the bleeder screw or turning the solenoid?
If yes there's a problem with the valve.

Wednesday, July 25th 2018, 8:49pm

by RichMoney

If zone 3 is coming on all the time, then the master valve wiring is connected to it somehow. Either a short, bad splice, is there an extra wire in the controller you can wire zone 3 to?

https://sprinklerresource.com/

Wednesday, July 25th 2018, 2:41am

by mrfixit

There's a problem with the zone 3 valve? Yep, find the valve and replace or repair it or maybe just adjust it. Depends.

Tuesday, July 24th 2018, 11:28am

by apr201

One zone stays on when the master valve is on

I have a 7 zone area and when that master valve is engaged the designated zone turns on along with zone 3. No mater what zone I turn on zone 3 also come on. This doesn't happen if I disconnect the master valve wire leading to the pump. Any thoughts?