Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.
Attention: The last reply to this post was 1921 days ago. The thread may already be out of date. Please consider creating a new thread.
The last 4 posts
Thanks Guys, thats exactly what I needed
As far are the reducing T's. I would not change what you have, but if you are putting in something new it can't hurt to go to 1" . But your flow is pretty low, so you can't go wrong either way.
Backflow preventers have very high flow ratings, so you can feed 12 gpm from a 3/4-inch device
1" Backflow on a 3/4" Tee??
Hi There,
Our builder placed a 3/4" stub on our 1.25" copper mainline to the house. My per zone usage for a set of rainbird spray heads is just under 12 gpm for each of 2 seperate zones, the other 2 are both drip. The Total length of my Mainline run (to my valve box) is pretty small, maybe 60' straight to the backyard from the side of the house. The designers at Rainbird suggested a minimum of a 1" Backflow and I have a couple of question for ya'll
1) Do I need to replace the 1" x 1" x 3/4" reducing Tee with a [1" x 1" x 1" standard Tee], or can I connect to that 3/4 without too much worry?
2) there is currently a 3/4 backflow attached, courtesy of the builder for the front yard drip system (which they put in before the sale). Any chance I could simple stick with this or is rainbord right on track that I really need to move to a 1" backflow?
Thanks in advance!