You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 884 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 10 posts

Wednesday, June 27th 2012, 10:49am

by Wet_Boots

If the RPZ spits water and then stops releasing water, it is not malfunctioning.

Wednesday, June 27th 2012, 9:00am

by longdrive03

Took that sucker apart last night and cleaned, inspected and did everything I knew how to do. Installed it and it held tight until I turned off the sprinkler then it dumped again but not as heavy. Looks like I will get new one. Saw them online for $192.00 so that should fix the problem and free up my time . Thanks for your help WB.

Tuesday, June 26th 2012, 7:07pm

by longdrive03

Installed the relief valve seat last night but no change. I believe there is a check valve in line before the rpz. I will open it tonight and see how it looks. I will probably take everything apart and clean and reinstall and see how that works. Any tips appreciated.

Monday, June 25th 2012, 2:15pm

by Wet_Boots

the gel (food-grade silicone grease) is needed on the O-ring involved in the moving parts of the relief assembly, and not so much anywhere else

Monday, June 25th 2012, 1:39pm

by longdrive03

Thanks. I will probably get the relief valve seat replacement today and install it since it's the only new part not installed. I also didn't lubricate the o-rings with the supplied gel (intructions don't mention it) and I'll do that.



I replaced the check seat valve orings with round o-rings from Home Depot. Do I need to get different o-rings from my supplier? Thanks again.



Burning up in Arkansas.

Monday, June 25th 2012, 1:16pm

by Wet_Boots

I had a few RPZs prone to pulsing, on high-pressure supplies, and it was essential to crack open the top-mounted testcocks to bleed the air out (these were all Febco 825Y) - it's still okay for an RPZ to spit some water when a zone shuts off hard.

Monday, June 25th 2012, 1:02pm

by longdrive03

Thanks WB. Is there a link on this forum for flushing air out of system? So I would have two check valves upstream before 975? Is there a sequence to open/shut the valves to avoid discharge. I really appreciate your help. thanks

Monday, June 25th 2012, 11:58am

by Wet_Boots

Make sure all the air is out of the device. A last-ditch attempt to stop a pulsating discharge is a check valve added upstream of the RPZ

Monday, June 25th 2012, 10:34am

by longdrive03

NEED HELP ON THIS ISSUE

Hi guys, just joined. My 975xl froze winter before last and I replaced the first check valve section. Had a few discharges last summer but my sprinkler guy reworked the 975 and everthing was good. This spring the relief valve discharges came back. I just installed a repair kit and two new check valve seats (one had a 1" chip off the rim). Still have the same discharge when sprinklers not on (nothing when they are). Discharge is pulsing at first then gotes to steady. What else could I do besides buying new unit? Thanks for any suggestions.

Thursday, May 24th 2012, 8:14am

by GatorGuy

My general rule is that if any part of a backflow is damaged by freezing I replace the whole thing. There could be hidden damage that will show up later. Then the customer is upset with my work and expect me to warrant the parts I didn't replace because I said they were good.

It would cost you more to have a professional diagnose each part than to do a simple replacement.

You didn't include pictures. In many cases the homeowner can do their own replacement. It's not that hard.
Then have it tested.