Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 923 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 4 posts

Tuesday, June 12th 2012, 4:56am

by Wet_Boots

You aren't going to damage the pump by operating at higher pressure.

Monday, June 11th 2012, 7:55pm

by tedbrim

Thanks for the reply and input.
I do have "wiggle" room on the shut off - as I can go to 65-70 psi - but I am very hesitant to do this.
I understand about using the larger diameter pipe. Are you suggesting the entire zone be "repiped" to greater than the 1inch I currently have? Or just the supply portion to the anti-siphon control valves? Thanks again.

Sunday, June 10th 2012, 11:02am

by Wet_Boots

If the zone design doesn't have large enough pipe, you won't be able to push enough water through it to get the pump performance you want.

What is the shut-off pressure of the pump? You may or may not have some wiggle room to raise the pressure settings.

Sunday, June 10th 2012, 8:46am

by tedbrim

Design for higher elevation

I have 3 zones running off 2-HP pump with bladder. 2 zones (7 heads each - all 1 inch line, Nelson gear driven) are at same elevation as pump (with anti-siphon control valves 1 foot above) and operate correctly; that is, pump runs continously at ~50 psi for duration of cycle.
Zone 3 (7 heads - Nelson, 1 inch line also) is at elevation 12 foot higher than pump/bladder. Anti siphon control valve is also 1 foot above this. Problem is when this zone is running, pressure at bladder increse dramatically and goes to shut off point (~ 60 psi) and then pump recycles. Pump on-off is not good. I think the solution is to "get more water thru this zone" - by adding more heads and/or larger nozzles. I have added 4-5 more heads - and increased the nozzles size with no success. I can change the pump shut off pressure valve to >60 psi but am hestitant to do this.
What might be a viable solution?