Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 834 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 3 posts

Wednesday, April 11th 2012, 4:38pm

by philly56

Thank you.

Wednesday, April 11th 2012, 4:19pm

by GatorGuy

Using the Hunter tech handbook it looks like you'll be fine. They indicate closer to 16 but 15 would be a safer bet.

Wednesday, April 11th 2012, 12:55pm

by philly56

Flow rate

I have a 3 inch water meter with a 3 inch service line (type k copper) that runs into the building for about 30 ft. It then reduces down to 1.5" copper for 10 ft. They then tee'd off with 1" copper for 20 ft. The 1" is what is being used for the supply to the POC for design. I would assume that I use the flow rate of 1" copper at 7.5"/sec. roughly around 15 gpm. Would this be correct?