Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 952 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 3 posts

Tuesday, September 13th 2011, 6:27am

by CRI IRR

The problem could be that the port for zone 3 is not producing power for the valve. Try taking the wire out of zone 3 port and put in, say zone 2, and turn on zone 2. If valve works then it is the controller. If it does not work then you most likely have a broken wire somewhere on zone 3 wire.

Friday, September 9th 2011, 9:06pm

by Central Irrigation

I think you're testing the wrong wires.



You should be touching one prong to the common wire (in your case i'm going to assume white wire) and the other to the colored zone wire. I would recommend using a multimeter that you can test resistance with, though.



Activate zone 3 at the controller.

Test voltage at the valve with all connections tied together the way they were. It is important to test voltage under a load (selonoid attached) in order to get accurate readings.

Friday, September 9th 2011, 8:00pm

by tauruseth

One zone not working

(please forgive my technical terminology)
We have a Rainbird system (ESP - 6si, if it matters) and one of the zones (3) doesn't work. We did a little research and decided to replace the solenoid. New solenoid in place, and still not working.

However, when I was rewiring everything back together, I accidentally wired the new solenoid to another valve wire. The zone that was not working started up like a champ. But, another zone (2) stopped working. Upon realizing my error, I rewired everything correctly and now the original zone (3) isn't working again.

We have a cheap little voltage tester, but I haven't been able to get it to read anything. I tested it in an outlet and it lit up just fine. Perhaps I am not testing the correct wires? I touch one prong of the tester to the valve wire and one to the solenoid wire and I get nothing. By "valve wire" I mean each valve has a white wire coming out of it that connects to one of the solenoid wires.

This all might be moot as the more research I do, the more it seems to me that that valve is not getting power. If that is, in fact, the case, how do we go about repairing it? Thanks so much for any help or wisdom you can offer.