You are not logged in.

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 1164 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 8 posts

Friday, August 12th 2011, 6:30pm

by Wet_Boots

Who knows, maybe there's a model of controller so crummy that the 9V battery could make a difference, and I, for one, am glad to not know what it is.

Friday, August 12th 2011, 3:09pm

by Central Irrigation

Sorry to burst your bubble, but the 9V backup battery has nothing to do with the controllers ability to turn zones on and off. You must have touched something in the controller, bumped a loose wire, or moved a module. Either way, glad the problem is "fixed".

Friday, August 12th 2011, 12:11pm

by Gurpreet Singh (Guest)

Finally solved the problem

Last thing I did was to bring a new controller but before installation I tried one more thing.
I changed 9V battery in the controller and guess what . Both the new valve started working.

This was the last resort before changing the controller.

May be this info is helpful for anyone with similar problem.

Wednesday, August 10th 2011, 2:04pm

by Gurpreet Singh (Guest)

Sprinkler not allowing to pass through

The front 3 valves are connected to controller and they are working fine.

When I added 4th and 5th valve and connected it to timer both are having this problem.

If I am taking wire from 4th and 5th valve and connecting to front valve they work fine, it shows that they are getting enough current and amps to let the valve funtion properly.

Wednesday, August 10th 2011, 1:58pm

by mrfixit

The timer could be bad. Take the solenoid and touch it directly to the controller on the problem station number and the ground terminal. If it opens and closes real fast the timer needs replacing.

You could try hooking that valve up to another terminal and abandon the one it's hooked up to now as a temporary fix.

Wednesday, August 10th 2011, 1:47pm

by Gurpreet Singh (Guest)

Sprinkler not allowing to pass through

I tried cleaning valve and put it back togather.

One more thing, when I took out the solenoid and connected it to the zone, the solenoid is opening and closing fast and making puttering noise ( like frog).

Is the solenoid bad?

In fact I used another solenoid but it is also doing the same thing

Wednesday, August 10th 2011, 12:50pm

by Wet_Boots

Try using something like piano wire to probe the passageways under the solenoid.

Wednesday, August 10th 2011, 10:05am

by Gurpreet Singh (Guest)

Sprinkler not allowing to pass through.

Hi,

I installed 2 hunter 1" inline - jar head valve. When I manually turn on, all the sprinklers work but when I turn on through controller the valve is making puttering noise and not allowing to pass the water through. When I turn on the bleed and let the water flow through bleed all the sprinklers pop up.

I changed the new solenoid but couldnt fix the problem.

In order to check if it is getting enough power, I connected the it to another rainbird valve and it works but this hunter valve refuse to work.

Please help, I am getting crazy going back and forth