Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.
Attention: The last reply to this post was 680 days ago. The thread may already be out of date. Please consider creating a new thread.
The last 6 posts
Replaced the start-up capacitor and it works like the day it was new. $5.17 sure beats the heck out of the $750 I was getting quoted for installation of a new pump! Thanks a lot for your suggestion.
Thanks, I'll give that a try and see what happens...
Maybe it needs a new starting capacitor.
Berkeley Pump S39518 Wont Start
Yes, its a booster pump and is correctly configured and wired for 120V. It ran fine for about 6 years, then started acting as described late last year. Ran fine the first few times this year but is now behaving the same way.
So this is a booster pump? And it is correctly wired to use 120 volts?
You might get a clamparound ammeter and read currents to the pump motor.
Berkeley Pump S39518 Wont Start
I have a Berkely S39518 pump with PSR-22 Pump Start Relay. Controller and PSR seem to be working fine, as I can see 120V at the pump motor terminals. I hear a buzzing from the motor for about 3 seconds but it won't kick on, then buzzing stops. This repeats every few minutes. It's almost like the pump motor tries to start, then some kind of protection circuit shuts it down. Occasionally (but rarely), it will kick on and everything's fine. Everything else seems to be OK, as it runs fine through all the zones, there's just very low pressure since the pump doesn't start. Any ideas?