Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 1532 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 5 posts

Thursday, May 20th 2010, 9:44am

by Wet_Boots

If using 9-volt batteries to trigger a solenoid, it would be more customary to use two batteries in series, to eliminate the possibility of overloading a solenoid. In fact some makes of solenoids note that they will function on 12 volts DC, if the supply pressure isn't too high.

Thursday, May 20th 2010, 8:31am

by HooKooDooKu

One of the easiest ways to determine if there is a problem with the controller is to take it totally out of the loop. Connect the wires for one valve directly to the transformer that powers the controller and see if the valve turns on without the controller. Of course there's always a chance there's something wrong with the power source (bad transformer, GFCI receptical that has popped, etc). So one other option to completely remove the power source and controller from the equation is to try three 9 volt battereis. Connect 3 batteries in series to get the 27 volts needed to open the valve. If you can't open it with batteries, then your batteries are bad, the selinoid in the valve is bad, or there's a problem in the wiring.

Wednesday, May 19th 2010, 9:43pm

by pass1

First check the voltage at the controller terminals for each zone. Should be around 27- volts AC. That will tell you if you have juice coming out of the controller. Not too familiar with the SRC, but as far as the rain sensor goes, when you disconnect the wires from the rain sensor terminals, I believe you will still have to run a jumper wire across those two terminals or insert a jumper clip that comes with the controller.

Wednesday, May 19th 2010, 9:36pm

by Wet_Boots

Test your wiring for resistance and continuity.

Wednesday, May 19th 2010, 7:18pm

by svsprinklers

SRC Control problem I Think??

I have a src with a rain sensor I bypassed sensor by connecting wires together and reconnected all wires but the valves will still not come on. How do you check if controller is bad? I did check the fuse and checked out fine. Any suggestions before ordering new controller?