You are not logged in.

  • Login
  • Register

Reply

Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 10 posts

Thursday, November 8th 2012, 6:41pm

by Wet_Boots

RE: Irritrol Junior Max, 6 stations

Absolutely hate it. No clear instructions. Yes, I know I can download a manual. I do not wish to deal with sprinkler company.

Can someone recommend a reliable, no brainier?
Thanks!
Consider a Hunter XC-600 - it looks a bit toy-like (they want you to spend more for a bigger controller :)) but it performs all the essential functions

Thursday, November 8th 2012, 4:39pm

by Annie (Guest)

Irritrol Junior Max, 6 stations

Absolutely hate it. No clear instructions. Yes, I know I can download a manual. I do not wish to deal with sprinkler company.

Can someone recommend a reliable, no brainier?
Thanks!

Wednesday, May 30th 2012, 1:19am

by Slundi (Guest)

Flashing 24V

After changing all the 3 Electolyts and and the power resistor it started working fine first but after a while (~1h) the 24V problem came back. I contacted technical support and they suggested to replace the controller because this problem msot probable hit the processor.

The Zener voltage is 9.32V



I gave up with this product and will go for another, more reliable one.

Monday, May 7th 2012, 2:46pm

by harmi (Guest)

The end

I gave up and today ordered different type/brand of controller.

Tuesday, May 1st 2012, 11:06am

by harmi (Guest)

Slundi thanks, I will give last chance to correct value of mid capacitor (I put 470uF/35 instead of original 220uF/50V and measured there >70V and capacitor was hot). If this does not help, looking for new controller, this does not make sense. PH.

Thursday, April 26th 2012, 2:28am

by Slundi (Guest)

Harmi, I wil try to emasure the Zener voltage over the weekend. Original electolyts (from top to down): C9=100uF,16V,85C; C7(middle one)=220uF,50V,85C ; C8=470uF,16V,85C

Wednesday, April 25th 2012, 5:15pm

by harmi (Guest)

Well, unfortunately I have further problems and partially similar to huflyer mentioned earlier. Multiple zones goes on concurrently. This seems some overheating issue, after power off and some break it gets corrected, but around 4th-5th zone (~15-20mins) it creates multiple zone problem. I pulled out PCB from box and testing now on desk. I realized that middle electrolyt (after replacements I put there 470uF/35V) is warm. But heating resistor is not the reason. I realized that voltage on this Cap is 33V= and 73V~?!?!, which I cannot understand. I need try different multimeter to verify AC value. Also ZD1 (located between red LED %scaling and PROG button) is overheated, PCB under it is already darker than the rest. I think R5 is 330R.

Although I do not think that the problem could be with precise capacity, could you pls share values of original electrolyt capacitors as I replaced one or two with not exactly same value. And also could you pls measure voltage on ZD1, whether it is 9.3V= or so. I will give some further tries, but already losing patience with such crappy tech design. But I have no ilusions that TORO or someone else will have much more reliable device, but this combination of power resistor and electrolyts is really great idea :-(

Tuesday, April 24th 2012, 4:55pm

by Slundi (Guest)

Flashing 24V problem

I have exactly the same problem with flashing 24V sign and no output power to solenoids. The PCB at the zener and at high power resistor is burnt. Thanks for sharing the issue with electrolyts because I wanted to replace the resistor only. Now I plan to replace all the 3 eletrolyts and the resistor.



Does anybody know the color codes on R5 resistor, the big one at the elecrolyts? Colors are not really visible on my component and I am not sure it kept the original value while overheated. I measured 151 Ohm.

Sunday, March 25th 2012, 3:28pm

by harmi (Guest)

24V flashing

I cannot believe that someone can place 3 electrolyts just next to
heating resistor. This is clear indication that we should buy a new one
after 3-4-5 years and preferably of different brand. In my case 24V
started flashing during last year, but everything worked as it was
supposed to, so I left it. However, today I realized that it
does not work - display OK (apart from 24V), but there was no voltage on 1-8 outputs. I have read this
thread, wrote down Start times and Run times for particular zones, reset
unit completely, left it without power for some time, but it did not
help and finally de-installed unit. During opening i saw that right upper
screw was not fixed, because plastic thing around was burned out -
brown and fragile. 24 V did not go through joint of power resistor on
PCB, so i re-soldered it, but no luck with function, there was also
something else. Then I concentrated on already mentioned 3 capacitors
and decided to replace them completely - they are only 85 rated,
fortunately I found 105-centigrade ones in my spares. After another
reset it seems working fine on my workbench, also 24V disappeared and hopefully no surprise will occur when installed finally. And I have cut a square hole approx.
15x18mm in the cover next to hearing resistor. For the winter I will
unplug it completely, but I think that this ventilation hole will reduce
the temperature inside to acceptable level.

Monday, September 12th 2011, 4:30pm

by huflyer (Guest)

burnt pcb

I have the same problem.

I disassembled the controller and realized, that the pcb is burnt in two areas:

1. in top-right corner (large resistor and 3 capacitors around it)
2. below the leds, under the zener-diode

I replaced the capacitors and switched on the 24VAC. The resistor became hot in 1 minute and 24VAC started flashing.
At that moment I realized, the the zener-diode became also hot, which is a surprise for me, because zener-diodes have typically 10mA current....

Desoldering the zener-diode and giving the 24VAC, the controller worked as before (bad), but one of the electrolit condenser became warm, so I unplugged it.

As there was no sign on the zener-diode I could not replace it and to tell the truth I think this problem is not the fault of the zener-diode, it only shows the fault.

Because the controller is full with SMD parts and there is no documentation I do not really think, that I will spend my time with debugging. It is cheaper to buy another type of irrigation timer... :(